6 COMMISSIONING
6.1 General Installation Check
The detector should have been installed as detailed in Section 4 and Section 5, which
include the appropriate adjustments for the tilt / alignment to the specific point on the
road surface or crossing area.
Before applying power to the Detector, ensure that the following checks are undertaken:
Detector power leads are connected to the correct terminals within the pole;
The correct detector relay outputs are used. For a standard detector (UK
Variant) these are usually blue and white (i.e. closed for detect);
The detector basic configuration dual-in-line switch located on the Digital PCB
has been set correctly (refer to the sections specific to the detector).
Note: In most instances the default setting, all off (0), will be the correct setting, unless
special circumstances apply. See the specific installation instructions for each particular
detector to determine the correct setting.
The Serial Communications interface terminations (if required) are connected to
the appropriate signal leads within the pole;
The Serial Communications interface Address Switch (if applicable) has been
set to the correct address for that particular communications line to the
associated controller (see Controller Configuration documentation).
The wireless interface MAC address label (if supplied) is stored in a suitable
location (e.g. the nearest traffic controller cabinet).