Specifications
Siemens Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 10 Page 69 of 120 Status Issued
Last Editor harry.smyth Date 03 November 2014
Document
Name
GENERAL HANDBOOK FOR HEIMDALL
DETECTORS
Doc. No.
667/HB/31900/000
Copyright Siemens plc 2014 All Rights Reserved
5.7.4 Detector Installation Instructions
Note: There must be no obstruction between the front face of the detector and the
detection zone, i.e. no obstruction by backing boards, signal aspects or foliage. Foliage
such as trees and bushes that are within the detection zone, will mean there is a risk of
false detects and possibly Permanent or no detect situations
Failure to adhere to these recommendations will reduce detector performance
5.7.4.1 Standard Detector Installation - Recommended
The standard traffic pole with the head mounted to one side is a suitable installation
scenario, where the aspect (traffic light) is mounted to one side of the detector location
and therefore provides for a clear view of the expected detection area.
In this situation the Kerbside should be mounted with the standard Kerbside mounting
bracket, which ensures the correct mounting distance in front of the nearside. The user
should reference Table 9-1 - p105 for part numbers.
Use of this bracket assumes that the pole has been installed with its mounting holes in
parallel to the kerb; if this is not the case then please see section 5.7.4.3.
Figure 25, below, illustrates the recommended detector and aspect configuration for all
new site installations that require a Heimdall detector Kerbside.
Figure 25 : Standard Pole configuration with Kerbside on Standard Bracket










