Specifications
Siemens Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 10 Page 68 of 120 Status Issued
Last Editor harry.smyth Date 03 November 2014
Document
Name
GENERAL HANDBOOK FOR HEIMDALL
DETECTORS
Doc. No.
667/HB/31900/000
Copyright Siemens plc 2014 All Rights Reserved
5.7.3 Operating Current
The overall operating current will depend whether any additional facilities are provided.
Table 5-26 below lists the typical current requirements:
24V AC Supply 167mA
24V DC Supply 131mA
Table 5-26 – Pedestrian Kerbside Detector Operating Current
Note: When power is first applied to the detector the following surge currents are drawn
from the supply:
DC Supply: 3.2 Amps (max) for < 2ms when the supply is 29V DC.
AC Supply: 4.2 Amps (max) for < 2ms when the supply is 29V AC.
If the detector has additional facilities fitted then the currents listed in Table 5-27 below
should be added to those shown in Table 5-26.
Additional Facility
24 VAC
24 VDC
Siemens SiTOS Serial Interface
(connected)
6 mA 5 mA
Siemens Wireless Interface (connected) 11 mA 10 mA
Table 5-27 – Additional Facilities Operating Current
Refer to Section 10 for details on power and cable length calculations.










