Specifications
Siemens Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 10 Page 65 of 120 Status Issued
Last Editor harry.smyth Date 03 November 2014
Document
Name
GENERAL HANDBOOK FOR HEIMDALL
DETECTORS
Doc. No.
667/HB/31900/000
Copyright Siemens plc 2014 All Rights Reserved
5.6.4.6 Detection Fault Monitor
The detector has a fault monitor function. In the default mode, the detector will generate a
fault output (equivalent to a permanent detect) if the detector has not registered an
activation for a period of twenty hours.
This duration can be adjusted to a user defined value by setting DIP Switch 7 to ‘1’ (On)
and then using the terminal command DFM (reference section 7.7.4).
5.6.4.7 Detector Hold Time
The detector continues to hold the detector output for a default period of 600mS after
actual object detection has ceased. This can be adjusted to an extended period of
2000mS by setting DIP Switch 5 to ‘1’ (On).
5.6.4.8 Installation and Commissioning Guide
Once the detector has been installed the crossing coverage must be tested, this is done
by walking towards the detector.
For ease of use when testing with only one person the ‘Inline Installation Assistance
Cable’, can be used to allow the detect LED to be more visible. The user should
reference Table 9-1 - p105 for part numbers.
(1) From a standing position several feet back from the kerb, walk along each dotted
white line either side of the crossing towards the detector.
(2) The detector should start to detect as you step off of the kerb until you get near to
the opposite side in both cases. If this is not the case re-align detector and start
perform step (1) again.
(3) Again from a standing point several feet back from the kerb, walk the centre of the
crossing towards the detector.
(4) The detector will probably pick you up before you leave the kerb, this is perfectly
normal, and should detect almost all the way across.
(5) Repeat these steps for the opposite detector to ensure the whole crossing is
covered.










