5.3.5 Side Access Configuration Dip Switch Settings
Note: Default settings are with all DIP switches set to ‘0’/ OFF.
Configuration
DIP Switch Number
1 2 3 4 5 6 7 8
Speed Threshold: km/h (Mph)
0,0,0,0 = 8 (5) 1,0,0,0 = 72 (45)
0,0,0,1 = 16 (10) 1,0,0,1 = 80 (50)
0,0,1,0 = 24 (15) 1,0,1,0 = 89 (55)
0,0,1,1 = 32 (20) 1,0,1,1 = 97 (60)
0,1,0,0 = 40 (25) 1,1,0,0 = 105 (65)
0,1,0,1 = 48 (30) 1,1,0,1 = 113 (70)
0,1,1,0 = 56 (35) 1,1,1,0 = 121 (75)
0,1,1,1 = 64 (40) 1,1,1,1 = Speed set by Eng. Terminal
O/P Hold Time
0 = Standard
‘hold time’ of
1000mS applies
1 = Terminal
applied ‘hold
time’ applies
Detection Range
0 = Full
1 = Reduced
DFM
0 = Default
monitor time
(20 hours
inactivity)
1 = ‘fault monitor
time’ is set by the
Engineer’s
Terminal
Remote
Configuration
0 = Disabled
1 = Enabled
Note: Some DIP switches may be marked with ON/OFF. For the purposes of definition, OFF is equal to 0 and ON is equal to 1
Table 5-12 – Variable Speed Threshold VA Detector Configuration Switch Settings
Refer to section 5.6 for detailed information regarding final commissioning.