Specifications

Siemens Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 10 Page 40 of 120 Status Issued
Last Editor harry.smyth Date 03 November 2014
Document
Name
GENERAL HANDBOOK FOR HEIMDALL
DETECTORS
Doc. No. 667/HB/31900/000
Copyright Siemens plc 2014 All Rights Reserved
5.1.4.4 Detector Alignment - Default
The detector uses a movement detection algorithm. Thus, the detector is aimed towards oncoming traffic
and towards the centre of the centre of the carriageway, at a position approximately 25 metres from the
associated ‘stop line’, as shown in Figure 14 below.
Figure 14 – Standard VA Detector Installation – Plan View
5.1.4.5 Detector Range - Default
The detector uses a movement detection algorithm. The range is typically set by the
appropriate angle and installation height. If the user requires a significant reduction in the
detection range (sensitivity), the detector configuration may be adjusted using DIP switch
6 (reference Table 5-4 below). Alternatively the terminal command RGE could be used
(reference section 7.7.4). The default setting is set for maximum sensitivity.
5.1.4.6 Detector Fault Monitor (DFM)
The detector has a fault monitor function. In the default mode, the detector will generate a
fault output (equivalent to a permanent detect) if the detector has not registered an
activation for a period of twenty hours.
This duration can be adjusted to a user defined value by setting DIP Switch 7 to ‘1’ (On)
and then using the terminal command DFM (reference section 7.7.4).
Approx. 10M
Approx. 25M from Stop Line
Approx. 35M from Stop Line
Typical Detection
Zone
Direction of
Travel
1 or 2 Lanes
of Apprroach
Typical Aiming
Point for Detector
Detector Mounted
on top of Signal
Alternative Position #3
(not recommended)
Drawing: Not to Scale
Position #1
(preferred location)
Alternative
Position #2