5.1.3 Operating Current
The overall operating current will depend whether any additional facilities are provided.
Table 5-2 below lists the typical current requirements:
24 VAC Supply 143 mA
24 VDC Supply 113 mA
Table 5-2 – Standard VA Detector Operating Current
Note: When power is first applied to the detector the following surge currents are drawn
from the supply:
DC Supply: 3.2 A (max) for < 2 ms when the supply is 29 VDC.
AC Supply: 4.2 A (max) for < 2 ms when the supply is 29 VAC.
If the detector has additional facilities fitted then the currents listed in Table 5-3 below
should be added to those shown in Table 5-2.
Additional Facility
24
VAC
24
VDC
Siemens SiTOS Serial Interface
(connected)
6 mA 5 mA
Siemens Wireless Interface (connected) 11 mA 10 mA
Table 5-3 – Additional Facilities Operating Current
Refer to Section 10 for details on power and cable length calculations.