The calculations may be worked out using the tabular form shown below:
Cable
1
Cable
2
Cable
4
Cable
3
Current
+ + + =
Total
Current
x Rs =
Volts
=
Volts
- 19. 2 =
Amps
=
(Transformer
voltage drop)
(Maximum allowable
Voltage drop in any cable)
(Lowest transformer
voltage)
Maximum allowable
cable length =
Voltage drop
in Cable 1
Metres
(Cable 1)
X 0.042 =
(or 0.021 for
conductors in
parallel
Vs (min) -
Table 12-3 - Calculation of Maximum Cable Length (Controller-mounted AC supply)
Note: The above chart yields the maximum length of one cable. The calculation within
the dashed area must be repeated for the other cables.