Specifications
Siemens Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version  10  Page 115 of 120  Status  Issued 
Last Editor  harry.smyth    Date  03 November 2014 
Document 
Name 
GENERAL HANDBOOK FOR HEIMDALL 
DETECTORS 
Doc. No.
667/HB/31900/000 
Copyright  Siemens plc 2014 All Rights Reserved 
12 CALCULATING PERMISSIBLE DETECTOR SUPPLY 
CABLE LENGTHS 
This section can be used to calculate the permissible cable lengths for non-standard 
installation requirements, for example the ST900 ELV detector supply kits. 
12.1 General Considerations 
When considering power supply needs for the Heimdall detector, care must be taken to 
ensure that all power losses are taken into account. This is particularly true for supply 
feeder runs to each detector. 
The following rules must be followed for each installation: 
  The minimum allowed voltage at any time on any detector is 19.2 volts 
  This voltage applies at the minimum mains voltage of 207 volts (which is -10% on 
the standard European voltage of 230v or -13.75% on the standard UK voltage of 
240v). 
 This voltage applies when the transformer is loaded with all the installed 
detectors volts (if applicable). 
  The detector interface cable resistance must be allowed for in calculating the 
maximum permissible cable lengths. 
The following fixed parameters will need to be applied to all calculations: 
  The supply and return resistance for a 1 mm2 cable is 0.042 ohms per metre. 
  Transformer secondary winding resistance 
  Worst case no-load voltage 
  Maximum supply current. 
For the Siemens supplied 24 AC Detector Transformers the following table can be 
consulted. 
Kit
160VA LV Supply
667/1/20292/008 
50VA LV Supply
667/1/27853/000 
Transformer Part Number  667/7/15855/005  667/7/00977/007 
Resistance  Rs  0.309 ohms  1.3 ohms 
Worst case no-load 
voltage at 207 volts 
mains (i.e. 230v -10%) 
Vmin  21.26v  23.13v 
Maximum current  Imax  6.6 A  2 A 
Table 12-1 – Siemens AC Detector Supply Specification 










