11 PERMITTED CABLE LENGTH ‘LOOK-UP TABLES’
This section assumes that the standard Siemens 24v AC Detector Supply transformer is
used.
The standard Siemens part numbers of the controller mounted AC Detector Supply kits
are assumed to be as follows.
Nominal 50VA, (2 amps) 667/1/27853/000
Nominal 160VA, (6.6amps) 667/1/20292/008
The following tables are provided to enable a very quick assessment to be made of the
suitability of a particular AC supply transformer and the required loading/cable runs.
These tables err on the ‘safe side’ and if particular installations do not fit the scenarios
presented then you will have to carry out the detailed calculations described in Section
11.
How to use the tables:
Determine how many other detectors are connected to the particular transformer.
Select the most appropriate table based on ‘point 1’ above. If there is no exact match
with the tables given choose the next highest.
Determine how many detectors are to be connected to the cable in question.
Determine the required cable length.
The table can then be viewed to see if standard ‘Serial’ (S) or ‘Parallel’ (P) supply feeds
should be used. A ‘Blank’ box is shown for situations which cannot be supported and a
re-design is necessary or a more detailed calculation is required, as described in Section
11.
11.1 Cable Type
Throughout these sections it is assumed that the installation has been completed with a
supply and return cable of 1 mm
2
.