Fault
Log
Index
Description Mnemonic
Category
No. of
Fault
Data
Bytes
Description / Data Bytes Further Comments / Byte Parameters
14
EEPROM
Invalid
Fault Data
FLTD Software
0
Fault Log Data is invalid. CRC failure occurred on Fault Data Chunk in EEPROM
15
Detector Type
Error
DETT Software
0
Detector Type read from
EEPROM is invalid.
All three locations in EEPROM storing the Detector Type showed CRC
failures. Detector goes into Detector Type Input Mode. This should occur at
production time only.
16
Soft Error SOFT Software
0
An undetermined firmware
error occurred
The external watchdog has not been reset (kicked) in time (1.6 sec).
17
Boot Loader
Error
BTLD Software
2
Boot Loader CRC failed
Byte 0: Boot Loader Version
low byte.
Byte 1: Boot Loader Version
high byte.
The F/W checks the integrity of the Boot Loader during initialisation. This
fault can be registered only if the Boot Loader at least managed to
positively check and start the F/W. If this fault occurs the Boot Loader has
to be reprogrammed as soon as possible!
Parameters: Current revision of the Boot Loader Firmware (in Flash
Section A).
18-22
Reserved for
future use
23
Latest Power
Up
LPRU Info
0
Power Up indication. This
information code is used to
log when the last power
cycle occurred.
In order to be able to monitor power-ups this information fault code has
been introduced. The time stamp of this information fault code indicates
the time of the last power-up with respect to the “operating hours counter”.
Since this is provided for information only, the status flag of this fault will
always remain cleared.