User manual

Siemens BACnet VAV Actuator Owner’s Manual
Siemens Building Technologies, Inc. 3
Digital
Application
Autozero Module (AZM) (optional)
2560, 2561, 2562, 2563
Damper Actuator
All
Fan
2565, 2566, 2567
First valve actuator (required)
2563
Second valve actuator (optional) or AZM (optional)
2563
Stage 1 electric reheat; or, 2-position heating valve
2562
Stage 1 electric reheat
2564, 2566
Stage 2 electric reheat (optional)
2562, 2564, 2566
Stage 3 electric reheat (optional)
2562, 2564, 2566
Valve actuator
2565, 2567
Power Wiring
The controller is powered by 24 Vac. Power wiring connects to the two screw
terminals on the controller labeled “C” (Common) and “H” (Hot) on the terminal block
labeled “24 VAC”. No earth ground connection is required (Figure 2).
24VAC Line
24VAC Neutral
Earth
Neutral Bond Wire
Dependent On
Local Codes
Required If Primary
Is Over 150 VAC
TEC05next#R1
24V
Figure 2. Power Wiring.