Specifications

Setting Room Temperature Setpoints
9
Siemens Industry, Inc.
140-0893 Start-up
Draft
1/12/2010
Setting Room Temperature Setpoints
Day (or occupied) cooling setpoint: DAY CLG STPT
Day (or occupied) heating setpoint: DAY HTG STPT
Night (or unoccupied) cooling setpoint: NGT CLG STPT
Night (or unoccupied) heating setpoint: NGT HTG STPT
1. If the room temperature sensor has a setpoint dial that will be used, set STPT DIAL
to
YES. Otherwise, set STPT DIAL to NO.
Set RM STPT MIN and RM STPT MAX for the minimum and maximum
allowable room temperature setpoint values, respectively. Valid values range
from 55° to 95°F (13° to 35°C). Default values are 55°F (13°C) for RM STPT
MIN and 90°F (32°C) for RM STPT MAX.
2. Setpoint dial configured with a heating/cooling deadband (default).
To allow the controller to operate with a heating/cooling deadband (functioning
the same as provided when the setpoint dial is not present) the following
configuration should be used.
Set the DAY HTG STPT less than the DAY CLG STPT by the deadband (or
zero energy band) that is desired. (for example, DAY HTG STPT = 70°F; DAY
CLG STPT = 74°F, providing a deadband of 4 degrees). Only the difference
between these values is used to determine the setpoint that will be used.
As described below, the setpoint(s) for heating/cooling will be 1/2 of the
deadband above or below the setpoint dial value.
When HEAT.COOL equals HEAT, then:
CTL STPT will equal RM STPT DIAL 0.5 * (DAY CLG STPT DAY HTG
STPT) and will be limited by RM STPT MIN and RM STPT MAX.
When HEAT.COOL equals COOL, then:
CTL STPT will equal RM STPT DIAL + 0.5 * (DAY CLG STPT DAY HTG
STPT) and will be limited by RM STPT MIN and RM STPT MAX.
NOTE: A space where the deadband is used can be more energy efficient than
a space where the deadband is not being used
3. Setpoint dial configured for zero heating/cooling deadband.
When the job specification requires a common heating and cooling temperature
setpoint, the following configuration should be used.
Set DAY HTG STPT equal to DAY CLG STPT. This will configure the setpoint
deadband equal to zero.
In addition, when a setpoint deadband equals zero, then:
CTL STPT will equal RM STPT DIAL, and will be limited by RM STPT MIN and
RM STPT MAX.
NOTE: A space where the heating/cooling deadband is zero may be more