Specifications

Setting Number of Heat Stages
7
Siemens Industry, Inc.
140-0893 Start-up
Draft
1/12/2010
Specifying Motor Setup
MTR SETUP determines which actuators are controlled by the application and whether
they are direct or reverse acting. Set MTR SETUP according to Table
MTR SETUP
Values
.
NOTE:
When MTR SETUP is changed, all enabled actuators will calibrate. Wait until
each actuator has completed its calibration before continuing.
MTR SETUP Values
Motor 1 (Damper)
Enabled Enabled and Reversed
Motor 2
Not Used 1 (default) 3
Enabled 5 7
Enabled and Reversed 13 15
Verifying Actuator Setup
1. Command all actuators closed. Verify that they close and remain closed. If not,
adjust the setting for MTR SETUP according to Table
MTR SETUP Values
.
2. If any of the actuators still do not close completely, then the actuators have been
installed or set up incorrectly. See the installation instructions (550-031), the iKnow
Troubleshooting Tool, or contact Field Support.
Setting Number of Heat Stages
Depending on the application, HTG STG CNT (if present) refers to electric heat stages
used (enabled), some point names may vary.
For electric heat applications, check the hardware to verify the number of electric
heat stages wired to the controller (1 to 3 stages without fan or 1 to 2 stages with
fan) and set HTG STG CNT to this value.
CAUTION
For installations using electric heat coils, never set min airflow settings to 0.
Equipment damage can occur if electric heat is on without airflow.