Specifications

Setting Controller Address
5
Siemens Industry, Inc.
140-0893 Start-up
Draft
1/12/2010
Setting Controller Address
Set CTLR ADDRESS to the BACnet MS/TP MAC address. (0 through 127 = Master;
128 through 254 = Slave).
NOTE:
Set the controller address and MS/TP network baud rate prior to connecting the
controller to the network. See Configuring BACnet Parameters [ 16].
Setting the Application
Add the TEC to your job database and select one of the following applications.
Application Description
Application Number
VAV Cooling Only 2860
VAV Cooling or Heating 2861
VAV with Electric Reheat or Baseboard Radiation 2862
VAV with Hot Water Reheat 2863
VAV Series Fan Powered with Electric Reheat 2864
VAV Series Fan Powered with Hot Water Reheat 2865
VAV Parallel Fan Powered with Electric Reheat 2866
VAV Parallel Fan Powered with Hot Water Reheat 2867
VAV Slave Mode 2897
After you set the application, sensor altitude, tubing length, tubing internal diameter,
UI1 and UI2 configuration point, the controller goes through a shut-down/load
sequence as it switches from slave mode to the application selected. After the
application loads, the calibration cycle begins.
At the start of the calibration cycle, the controller automatically sets CAL AIR to YES.
When the cycle is complete, CAL AIR returns to NO.
The air velocity sensor calibration cycle begins within three minutes of an application
start-up or initialization, depending on the controller’s address. After this delay, the
calibration cycle takes from 2 to 5 minutes to complete. The air damper closes during
calibration.
NOTE:
You can continue the startup procedure while calibration is underway. However,
the controller will ignore commands to control end devices (such as the damper)
until calibration of the air velocity sensor is finished.