Specifications
Setting Room Temperature Offset (optional)
15
Siemens Industry, Inc.
140-0893 Start-up
Draft
1/12/2010
Setting Room Temperature Offset (optional)
When the room has stabilized, take a precision temperature reading over a period of
time at the room temperature sensor, record any difference between this reading and
the value of ROOM TEMP and set this difference value (to the nearest 0.25°F
(0.14°C)) into RMTMP OFFSET.
Example
If the actual room temperature is 72.0°F (22.2°C), and the value of ROOM TEMP is
73.0°F (23.8°C), then the value entered into RMTMP OFFSET is –1.0. In this case, the
value of ROOM TEMP would read the raw value 73.0°F (23.8°C), but the value of CTL
TEMP would read 72.0°F (22.2°C).
CTL TEMP = ROOM TEMP + RMTMP OFFSET