Specifications
Configuring the Room Unit
10
Siemens Industry, Inc.
140-0893 Start-up
Draft
1/12/2010
comfortable than a space where the deadband is being used, but may use more
energy.
4. Set the room temperature setpoints to the desired values. Heating setpoints are not
present in cooling only applications.)
Configuring the Room Unit
STAT SUPV values are additive; set STAT SUPV to the sum of the configured
selection. A value of 3 indicates the stat has both humidity and temperature..
0 - for the Sensing only Room Unit.
1 - for communicating Room Unit with Full featured Room Unit.
2 - for communicating Room Unit with humidity.
Setting Override Time
If using night/unoccupied override, set OVRD TIME to the number of whole hours that
an override should last. If OVRD TIME equals 0 (default), this feature is disabled.
Configuring Universal Inputs (UIs)
Configure each Universal Input; using one of the following options for each UI.
(UI1 CFG, UI 2 CFG)
0 - DI
1 - 10K (Temperature thermister)
2 - 0-10V (0 to 100%)
3 - 4-20mA (0 to 100%)
NOTE:
The controller goes through a shut-down/load sequence after setting.