Operating instructions

e1955
11.1999
8
Siemens Building Technologies
Cerberus Division
Message categories
There are the following message categories:
Alarms danger messages acquired by the system Priority 1
Faults messages that require an immediate response Priority 2
Isolation system components out of service Priority 3
Information messages that do not require an immediate response Priority 4
123
456
789
ok
F2
F1
0
C
AlgoRex
R
Alarms FaultsIsolationInformation
Alarm device Alarm deviceAlarm devicePremises
active faultisolate(d)manned
Remote alarm Remote transmissionRemote alarmAlarm delay
active faultisolate(d)off
Mains SystemControl functionDetector
available faultisolatedtest mode
ISOLATERESETACK
EXT BELL
ISOLATE
WARN SYS
ISOLATE
NEXTPREV
BELL
EXT
ISOL
SYS
WARN
ISOL
ISOL
FAULT
ALARM
FIREFIGHTER FACILITY
1
2 3 4 5 6 7 8
F1:function ok:interv.text F2:menu
main building / 1st floor
room 104
Fire brigade REQUESTED Zones: 1
01 AUTOM. ALARM SMOKE NACK
F1:function F2:menu
room 104
01 detector
FAULTS Zones: 1
F1:function F2:menu
room 104
01 detector
ISOLATION Zones: 1
F1:function F2:menu
room 104
01 detector
main building / 1st floor
main building / 1st floor
main building / 1st floor
Information Total: 1
1 Information display field
Press key
2 to display the information list.
Certain information messages are displayed spontaneously (e.g. warnings) if no message with a higher priority
is pending.
3 Isolation display field
Ü The indicator is blinking if there are unacknowledged messages in then list
Press key
4 to display the list of disabled system components.
This message type is displayed spontaneously if no message with a higher priority is pending.
5 Alarms display field
Ü The indicator is blinking if there are unacknowledged messages in then list
Press key
6 to display the list of alarms.
This message type is always displayed spontaneously and overwrites all other message categories
7 Faults display field
Ü The indicator is blinking if there are unacknowledged messages in then list
Press key
8 to display the list of existing faults.
This message type is displayed spontaneously if no message with a higher priority is pending.
Note
Switching from one message category to another is always possible by pressing the corresponding selection
key. If a lower priority is selected, the system always goes back after a short time-out, to that message category
with the highest priority.