Operating instructions

e1955
11.1999
6
Siemens Building Technologies
Cerberus Division
Control console layout
123
456
789
ok
F2
F1
0
C
AlgoRex
R
Alarms FaultsIsolationInformation
Alarm device Alarm deviceAlarm devicePremises
active faultisolate(d)manned
Remote alarm Remote transmissionRemote alarmAlarm delay
active faultisolate(d)off
Mains SystemControl functionDetector
available faultisolatedtest mode
ISOLATERESETACK
EXT BELL
ISOLATE
WARN SYS
ISOLATE
NEXTPREV
BELL
EXT
ISOL
SYS
WARN
ISOL
ISOL
FAULT
ALARM
FIREFIGHTER FACILITY
1
2
3 4
5 6 7
8
9
10
11 12
13
14
15
16
Firefighter facility
Function key pad
01 manned
main building
INFORMATION Total: 1
F1:function F2:menu
17
18
17a
17b
17c
19
20
21 22
23
24 25
26
27 29
28
30
31
32
33
34
35
36
37
Special keys and indicators
Special keys and indicators
List Handling
1 Information indicator & key Information message list handling & indication see page 8
2 Isolation indicator & key Isolation message list handling & indication see page 8
3 Alarm indicator & key Alarm message list handling & indication see page 8
4 Fault indicator & key Fault message list handling & indication see page 8
Operating states
5 Premises manned indicator & key Premises manned / unmanned switch over & indication see page 11
Alarm devices
6 Alarm device isolate(d) indicator & key Isolation / deisolation of alarm devices see page 29
7 Alarm device active indicator & key Activation / deactivation of Alarm devices
8 Alarm device fault indicator Indicates fault of alarm devices
Remote Transmission
9 Alarm delay off indicator & key Immediately initiates the alarm remote transmission see page 16
10 Remote alarm isolate(d) indicator & key Disables alarm remote transmission see page 28
11 Remote alarm active indicator Indicates active alarm remote transmission
12 Remote transmission fault indicator Indicates faults of the alarm remote transmission
Control and System
13 Detector test mode indicator Indicates zones are in mode detector test see page 22
14 Control function isolated indicator Indicates isolated control functions
15 Mains available indicator Indicates main power supply normal operation see page 10
16 System fault indicator Indicates fatal system fault