Operating instructions

e1955
11.1999
34
Siemens Building Technologies
Cerberus Division
Event memory
Polling event memory of an AREA
1. Press
F2
Ü The MAIN MENU is displayed
2. Press
ok
Ü The AREAS overview is displayed
Press to select the desired AREA
3. Press
F1
Ü The FUNCTION LIST area is displayed
Press
to select «poll EVENT MEMORY»
4. Press
ok
Ü The FUNCTION LIST event memory is dis-
played
Press
, if necessary, to select the desired function
and press
ok
Ü The display now shows the desired list.
Either the latest entry is visible completely, older en-
tries (if existing) can be scrolled by pressing
Note
with
F2
:>date/time a entry of a
particular date/time can be selected and displayed.
Printing selected entries of the event memory
Steps 1..4 are identical to «Polling event memory of an area» as described above
5. Press
F1
Ü The printout EVENT MEMORY menu is dis-
played
Press
F2
to print all entries or
select desired range of date and time to print
out particular events.
Use
and to set date and time and press
F1
to
select the next field.
Press
ok
to print out selected entries.
Ü During the print out procedure on the bottom line
a flashingprinting in inverted coulors is dis-
played.
Note
The event memory can only be printed out, if the printer is connected to the operated terminal.
ok:execute F1:areas C:end
AREAS
01 main building
FUNCTION LIST area:
ISOLATE REMOTE transm. fire
^/v:scroll F1:print F2:->date/time
EVENT MEMORY
machine building
printout EVENT MEMORY
... printing ...
printout EVENT MEMORY
VV
02 machine building
03 warehouse building
poll EVENT MEMORY
DEISOLATE REMOTE transm. others
ISOLATE REMOTE transm. others
DEISOLATE REMOTE transm. fault
ISOLATE REMOTE transm. fault
ok:execute F1:areas F2:->date/time
FUNCTION LIST event memory:
poll all TEST-ALARM messages
poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
engine room
21-FEB-1996 11:26:43 INFORMATION
-detector zone INSTALL. TEST
machine building
compressor room
Printout starts at: 08:00 21-FEB-1996
Printout stops at: 08:00 21-FEB-1996
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
ok:select F1:function C:end
ok:set F1:next field F2:print all
ok:section F2:menu F1:function