Operating instructions

e1955
11.1999
30
Siemens Building Technologies
Cerberus Division
Printer ISOLATE/DEISOLATE
This system is equipped with a printer Yes
No
When does the printer have to be ISOLATED?
Normally the printer (if installed) operates in active stand-by. Isolation is needed only in special cases (for exam-
ple to change the paper). The printer can be isolated and deisolated via the menu. The «ISOLATED» state is
shown on the display.
ISOLATING the printer
1. Press
F2
Ü The MAIN MENU is displayed
With
choose the function «DEVICE level»
2. Press
ok
Ü The STATIONS overview is displayed
Press , if necessary, to select the desired station
(control unit or terminal)
3. Press
F1
Ü The FUNCTION LIST control unit is displayed
Press to select «ISOLATE printer» and press
ok
Ü The printer is isolated
DEISOLATING the printer
1. Press the Isolation key and select the desired
message by pressing
, if necessary. The se-
lected message is displayed in inverted colors.
2. Press
F1
Ü The FUNCTION LIST control unit is displayed
With select the function «DEISOLATE printer»
and press
ok
Ü The printer is deisolated
ok:execute F1:stations C:end
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
STATIONS
01 control unit CC1140 ground floor
set sound level of BUZZER
ISOLATION Zones: 0
reception ground floor
02 terminal CT11 corridor 1st floor
poll EVENT MEMORY terminal
DEISOLATE printer terminal
set contrast of DISPLAY
ok:execute F1:stations C:end
ok:select F1:function C:end
ok:funct.unit F2:menu F1:function
FUNCTION LIST terminal:
ISOLATE printer terminal
initiate LAMP TEST
F1:function F2:menu
01 printer terminal ISOLATED
ISOLATE printer terminal
poll EVENT MEMORY terminal
set contrast of DISPLAY
set sound level of BUZZER
ISOLATE printer terminal
DEISOLATE printer terminal
FUNCTION LIST terminal:
initiate PRINTER TEST terminal