Operating instructions

e1955
11.1999
28
Siemens Building Technologies
Cerberus Division
Remote transmission ISOLATE/DEISOLATE
This system is equipped with a remote transmission facility
for FIRE ALARM Yes, destination:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No
for FAULT Yes, destination:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No
What is «Remote transmission»?
Remote transmission establishes a transmission path to the fire department in the event of a FIRE ALARM.
For FAULT there is normally a separate path established.
When does the remote transmission have to be isolated?
Normally the remote transmission operates in active stand-by. Isolation is needed only in special cases, for ex-
ample for testing the control functions. For this test the
Remote alarm isolate key
1
on the control console
has to be pressed. The «ISOLATED» state is signalled by the indicator
2
.
123
456
789
ok
F2
F1
0
C
Alarms FaultsIsolationInformation
Alarm device Alarm deviceAlarm devicePremises
active faultisolate(d)manned
Remote alarm Remote transmissionRemote alarmAlarm delay
active faultisolate(d)off
Mains SystemControl functionDetector
available faultisolatedtest mode
2
1
ISOLATING the remote transmission
Press key
1
Ü The corresponding isolation message is displayed
Ü Indicator
2
turns on
Ü The FIRE ALARM remote transmission is isolated
DEISOLATING the remote transmission
Press key
1
(toggling key)
Ü Indicator
2
turns off
Ü The FIRE ALARM remote transmission is deiso-
lated and switched to stand-by
Note
The remote transmission can also be isolated and deisolated via the menu, separately for «Alarm» and
«Fault».
The remote transmission must be periodically checked by activating a manual call point. The fire department
must be notified before the test is initiated.
F1:function F2:menu
02 RT fire ISOLATED
factory
remote transmission channel FIRE
01 RT fire ISOLATED
remote transmission channel FIRE
main building
ISOLATION Zones: 0