Mode Installation test
What is the mode «Installation test» for?
The mode «Installation test» allows to test the correct function of the whole fire detection system including fire
controls, acoustical alarm devices, etc. All functions remain enabled.
Make sure that the remote transmission is isolated or the fire department is informed about the test activities.
In the mode Installation test interactive detectors become more sensitive and respond faster (response behav-
ior as in mode «Detector test»).
The mode Installation test shall be carried out only by security staff and serves basically to test the
alarm organization and fire controls.
After the test work has been completed immediately cancel the mode «Installation test».
Mode «Installation test» is normaly enabled and disabled on the level ZONE but also possible on the level
SECTION
Setting a zone to mode «Installation test»
1. Press
F2
Ü The MAIN MENU is displayed
2. Press
ok
Ü The AREAS overview is displayed
Press
to select the desired AREA
3. Press
ok
Ü The SECTIONS overview is displayed
Press to select the desired SECTION
4. Press
ok
Ü The ZONES overview is displayed
Press to select the desired ZONE
5. Press
F1
Ü The FUNCTION LIST zone is displayed
With scroll to the function
«set zone > INSTALLATION TEST» and press
ok
Ü The ZONE is set to mode «Installation test»
Termination of mode «Installation test» of a zone
1. Press the Information key and select the desired
message by pressing
, if necessary. The se-
lected message is displayed in inverted colors.
2. Press
F1
The FUNCTION LIST zone is displayed
With
scroll to the function
«set zone > INSTALLATION TEST OFF»
and press
ok
Ü The ZONE is set to normal operation mode
ok:element F2:section F1:function
ok:zone F2:area F1:function
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
AREAS
01 main building
SECTIONS
01 ground floor
02 1st floor
ZONES fire
01 room 101
03 lift shaft
04 2nd floor
fire
02 1st floor
03 storage room
04 conference room
05 corridor
ok:execute F1:zones C:end
FUNCTION LIST zone :
set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
activate FAULT TEST
set zone -> INSTALLATION TEST OFF
set zone -> INSTALLATION TEST
ok:section F2:menu F1:function
ok:select F1:function C:end
INFORMATION Total: 1
01 detector zone INSTALL. TEST
ok:execute F1:zones C:end
FUNCTION LIST zone:
set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
activate FAULT TEST
set zone -> INSTALLATION TEST OFF
set zone -> INSTALLATION TEST
main building / 1st floor
conference room
F1:function F2:menu