Operating instructions

e1955
11.1999
24
Siemens Building Technologies
Cerberus Division
Mode Detector test
cont.
Terminate «Detector test» for all
detector zones within a SECTION
1. Press
F2
Ü The MAIN MENU is displayed
2. Press
ok
Ü The AREAS overview is displayed
Press
to select the desired AREA
3. Press
ok
Ü The SECTIONS overview is displayed
Press to select the SECTION that is on detector
test
4. Press
F1
Ü The FUNCTION LIST section is displayed
With
select the function «terminate TEST of all
DETECTOR zones» and press
ok
Ü The «Detector test» is now cancelled for all de-
tector zones of this section
set all CALL POINT zones -> TEST
ok:execute F1:sections C:end
ok:zone F2:area F1:function
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
AREAS
01 main building
SECTIONS
01 ground floor
02 1st floor
FUNCTION LIST section :
DEISOLATE all DETECTOR zones
ISOLATE all CALL POINT zones
DEISOLATE all CALL POINT zones
set all DETECTOR zones -> TEST
terminate TEST of all DETECTOR zones
03 lift shaft
04 2nd floor
ok:select F1:function C:end
ok:section F2:menu F1:function