Mode ’Detector test’
What is the «Detector test» mode for?
The mode «Detector test» allows individual on-site function testing of automatic fire detectors and manual call
points without generating an alarm message.
Automatic fire detectors are actuated with a special detector tester.
Interactive detectors are set to the special parameter set ’Test’ in order to achieve a fast activation with the de-
tector tester.
Manual call points are activated depending on the type:
– From externally with a special test key without breaking the glass pane or opening the housing.
– Simply by opening the door of the manual call point.
Test alarm is the active state of automatic fire detectors or manual call points in «Detector test» mode. A test
alarm does not generate a danger message in the control console. That means that neither acoustical alarm
devices nor remote transmission or any other control functions are activated.
Test alarms are recorded in the event memory and logged spontaneously, if a printer is connected.
How to set detectors or manual call points to mode «Detector test»?
This is normally done on the section level, but also possible on the zone level.
It is not possible to set an individual fire detector or manual call point (element) to «Detector test».
Zones or sections set to «Detector test» are displayed spontaneously as a message in the category ’Isolation’
Set all detector zones within a SECTION to «Detector test»
1. Press
F2
Ü The MAIN MENU is displayed
Press
to select the desired menu item.
2. Press
ok
Ü The AREAS overview is displayed
Press to select the desired AREA
3. Press
ok
Ü The SECTIONS overview is displayed
Press to select the desired SECTION
4. Press
F1
Ü The FUNCTION LIST ’section’ is displayed
With
select the function «set all DETECTOR
zones –> TEST» and press
ok
(automatic detectors
only).
Ü All zones of automatic detectors that belong to
this section are set to «Detector test»
Indicator «Detector test mode» is on
Same procedure for manual call points
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
ok:select F1:function C:end
AREAS
01 main building
02 factory
ok:section F2:menu F1:function
ok:zone F2:area F1:function
SECTIONS
01 ground floor
02 1st floor
03 lift shaft
04 2nd floor
ok:execute F1:sections C:end
ISOLATE all DETECTOR zones
DE–ISOLATE all DETECTOR zones
ISOLATE all CALL POINT zones
DE–ISOLATE all CALL POINT zones
set all DETECTOR zones -> TEST
terminate TEST of all DETECTOR zones
FUNCTION LIST ’section’: