Data and design subject to change without notice. / Supply subject to availability. E Copyright by Siemens Building Technologies AG We reserve all rights in this document and in the subject thereof.
Operating instructions CI1145 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Control console layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Message categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction This Cerberus fire detection installation consists of the following components: System components Operating console Series of fire detectors ? Equipped Type ’CI1145’ Interactive detectors Addressable detectors Collective detectors Includes also extinguishing SECTIONS ? CO2 N2 water .......... yes Printer connected ? Location no .............................. ..............................
Operating access General: The control console is protected by a front door against unauthorized or unintentional manipulation. So no further password protection is necessary except for some special functions which are restricted to the service engineer. Possible access levels: Access level 1 Access level 3 Everybody Service access to all user functions full privileges (service engineer only) How to get USER operating access: Just open the front door.
Control console layout Firefighter facility FIREFIGHTER FACILITY 17 18 19 20 21 ALARM FAULT ISOL INFORMATION 01 manned main building EXT WARN BELL 22 SYS ISOL ISOL EXT BELL WARN SYS ISOLATE ISOLATE 23 Premises manned 9 Alarm delay off Detector 13 test mode AlgoRex R F2:menu 17c NEXT ACK RESET ISOLATE 25 26 27 28 29 Isolation 6 17a PREV Alarms 3 2 5 1 17b F1:function 24 Information 1 Total: Alarm device isolate(d) Alarm device active 11 Remote alarm active 12 Remote
Control console layout cont. Firefighter facility 17 Text display with yellow illumination. dark, if no danger message («Alarm») is pending and no operator activity is in progress. 17a Information bar Information is context dependent 17b Message part e.g.
Message categories There are the following message categories: Alarms danger messages acquired by the system Priority 1 Faults messages that require an immediate response Priority 2 Isolation system components out of service Priority 3 Information messages that do not require an immediate response Priority 4 FIREFIGHTER FACILITY ALARM Fire brigade REQUESTED 01 AUTOM.
Terminology ’Area’, ’Section’ and ’Zone’ What is an «Area»? It normally covers a whole building or part of a building and represents also the operating level. This is the logical designation for several, usually adjacent sections Area ’Main building’ AREA 01 main building 02 factory ok:section F2:menu F1:function What is a «Section»? It normally covers a floor or part of a floor in a building.
Normal operation / Mains available What is «Normal operation»? The system is ready for receiving danger messages No alarm and no fault messages are pending and no part of the system is isolated Ü The system can either be in state «manned» or «unmanned» (see page 11) Ü The operating states «manned» / «unmanned» are information messages.
Operating states ’manned’ and ’unmanned’ Is the Cerberus Alarm Concept activated? Yes No Basic rules The operating states «Manned» and «Unmanned» are only relevant for systems in which the signals for automatic fire detectors and manual call points are processed differently, that means, the Cerberus Alarm Concept is activated. The switchover can be performed manually or automatically. Operating state «manned» Means: The operating person responsible for «Alarm» investigation is on site.
Quick reference instructions How to start operating ? 1. Press F2 Ü The MAIN MENU is displayed 2. Select desired function in ’MAIN MENU’ by using and the arrow keys 3. Then press ok Ü option selected is shown inverse MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.
Cerberus Alarm Concept How does the Cerberus Alarm Concept function? When the system operates in «manned» mode, manual call points and automatic fire detectors trigger different actions in the event of an alarm.
Alarm – general information How are alarm messages shown in the text display? 1st alarm message Zone «Room 104» Room 103 Corridor Room 102 Room 103 2nd alarm message Zone «Room 102» detector type Fire brigade REQUESTED 01 AUTOM. ALARM SMOKE main building / 1st floor room 104 02 AUTOM. ALARM HEAT main building / 1st floor room 102 F1:function ok:interv.
Alarm – general information cont. Message order Messages are presented in the following order: 1. unacknowledged alarms 2. acknowledged alarms 3. isolated alarms Within these categories the messages are sorted chronologically. Acknowledge Ü Each message has to be acknowledged separately 1. Select the desired unacknowledged message 2.
Alarm – what to do ? Top line of display reports status of remote transmission: ’CALL fire brigade: TEL. 000’ ............ FIREFIGHTER FACILITY AlgoRex 1 ’FIRE BRIGADE in .... ’ ............ 3 Fire brigade REQUESTED ............ 2 " 'Fire brigade REQUESTED' Alarm is already transmitted 1. Press ACK for each pending alarm message 1 2. Read the fire location of the 1st alarm in the upper half of the text display field 3. Go to the fire location 4.
Alarm – what to do ? cont. What to do if alarm cannot be reset ? As long as a detector still detects a fire phenomena (smoke, heat, flame) the alarm cannot be reset. In order to remove such an alarm the corresponding detector zone has to be isolated. ZONE isolation procedure if zone is on alarm (Example ZONE ’fire’) 1. Select ZONE on alarm to be isolated ALARMS 01 AUTOM. ALARM SMOKE main building/1st floor conference room F1:function Zones: 1 ACKD F2:menu 2.
Detector zone, temporary isolation What is ISOLATION of a ZONE ? Isolated zones have the following characteristics: The zone state (alarm and fault) is evaluated and displayed Alarms on isolated zones do NOT activate any control outputs (e.g.
Detector zone, temporary isolation 5. Press F1 Ü The FUNCTION LIST ’zone’ is displayed Select the function ’ISOLATE zone’ Press ok to confirm Ü The selected ZONE is isolated Ü It is displayed spontaneously (if no messages of higher priority are pending). FUNCTION LIST ’zone’: ISOLATE zone DE–ISOLATE zone set zone -> TEST set zone -> TEST OFF activate ZONE TEST set zone -> RENOVATION ok:execute F1:zones ISOLATION 01 detector zone ISOLATED main building/1st floor conference room F1:function cont.
Isolation of individual detectors When does a detector have to be isolated ? Only when it is damaged or defective until it is replaced. Note An isolated detector cannot generate any messages. The isolation of detectors only makes sense if the corresponding ZONE is de–isolated Isolate a detector via the menu Steps 1 to 4 are identical to «Zone isolation» as described above 5. Press ok Ü The ELEMENTS summary is displayed Press to select the desired ELEMENT 6.
Fault What to do in case of reported fault messages? 1. Confirm the message by pressing ACK 2. Read the fault location on the display 3. Go to the fault location 4.
Mode ’Detector test’ What is the «Detector test» mode for? The mode «Detector test» allows individual on-site function testing of automatic fire detectors and manual call points without generating an alarm message. Automatic fire detectors are actuated with a special detector tester. Interactive detectors are set to the special parameter set ’Test’ in order to achieve a fast activation with the detector tester.
Mode ’Detector test’ cont. Recommendations for detector test Perform the function test periodically. The interval of this test is determined by the service engineer. Switch only the fire detectors of one SECTION at a time to «Detector test», never the entire building. For manual call points the function test needs to be performed only based on a spot-check. Test automatic fire detectors and manual call points of the same room always separately. Do not set them to «Detector test» simultaneously.
Mode ’Detector test’ cont. Terminate «Detector test» for all detector zones within a SECTION 1. Press F2 Ü The MAIN MENU is displayed 2. Press ok Ü The AREAS overview is displayed to select the desired AREA Press MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function AREAS 01 main building ok:section 3.
Mode ’Detector test’ cont. Poll ’test alarms’ in the event memory 1. Press F2 Ü The MAIN MENU is displayed to select DEVICE level Press 2. Press ok Ü The STATIONS overview is displayed Press to select the desired STATION MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function STATIONS 01 CC1142 CBUS no1 02 CI1142 CBUS no2 05 CT1142 CBUS no5 ok:funct.unit 3.
Mode ’Installation test’ What is the mode «Installation test» for? The mode «Installation test» allows to test the correct function of the whole fire detection system including fire controls, acoustical alarm devices, etc. All functions remain enabled. Make sure that the remote transmission is isolated or the fire department is informed about the test activities. In the mode ’Installation test’ interactive detectors become more sensitive and respond faster (response behavior as in mode «Detector test»).
Mode ’Renovation’ What is the «Renovation» mode for? In «Renovation» mode, automatic detectors are much less sensitive. This may be required while unusual work is in progress (e.g. during renovation of a building). The fire detection system remains working, the remote transmission of alarm and fault messages is enabled. Manual call points work as in normal operation mode. Detectors in the mode ’Renovation’ are from the insurance and approval point of view out of order.
Remote transmission ISOLATE/DE–ISOLATE This system is equipped with a remote transmission facility for FIRE ALARM Yes, destination: No for FAULT Yes, destination: No ............................................................................................... ............................................................................................... What is «Remote transmission»? Remote transmission establishes a transmission path to the fire department in the event of a FIRE ALARM.
Alarm devices ISOLATE/DE–ISOLATE When do alarm devices (horns, sirens, etc.) have to be isolated ? Normally the alarm devices operate in active stand-by. Isolation is needed only in special cases, for example for testing the control functions.
Printer ISOLATE/DE–ISOLATE This system is equipped with a printer Yes No When does the printer have to be ISOLATED? Normally the printer (if installed) operates in active stand-by. Isolation is needed only in special cases (for example to change the paper). The printer can be isolated and de–isolated via the menu. The «ISOLATED» state is shown on the display. ISOLATING the printer 1. Press F2 Ü The MAIN MENU is displayed With choose the function «DEVICE level» 2.
Printer B2Q191: paper replenishing Valid for this system Yes, system equipped with printer B2Q191 No printer of this type installed 1 Isolate the printer first Swing out printer unit 2 Remove the used paper roll ÎÎÎÎ ÎÎÎ ÎÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎÎ ÎÎÎ ÎÎÎ ÎÎÎ 3 5 Lift the paper flap and slide a new paper roll over the spindle The paper can be transported by means of the knurled wheel A 4 7 Press the winding up key De–isolate the printer 6 Press the leading edge of the paper lightly against the flap
Lamp test What is the «Lamp test» used for? For testing the correct functioning of all indicators (LEDs), the display, and the alarm buzzer. All visual and audible devices of the control console are activated for a few seconds. Initiate lamp test 1. Press F2 Ü The MAIN MENU is displayed With choose the function «DEVICE level» 2.
Alarm counter What is the purpose of polling the alarm counter? The alarm counter shows the number of past alarm events. Polling alarm counter 1. Press F2 Ü The MAIN MENU is displayed 2. Press ok Ü The AREAS overview is displayed Press to select the desired AREA MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function AREAS 01 main building ok:section 3.
Event memory Polling event memory of an ’AREA’ 1. Press F2 Ü The MAIN MENU is displayed MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function 2. Press Ü The AREAS overview is displayed to select the desired AREA Press ok C:end AREAS 01 main building 02 machine building 03 warehouse building ok:section 3.
Set clock and date Normally the date and time do not have to be corrected! The date and time are set by the service engineer when installing the system. The summer/winter time changeover is performed automatically. Time and date are always displayed when the password is entered. Setting the clock 1. Press F2 Ü The MAIN MENU is displayed 2.
Overview operating menus To enter ’MAIN MENU’ press F2 MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.
Overview operating menus To enter ’MAIN MENU’ press cont. F2 MAIN MENU FIRE section EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function Note F1 = press F1 ok = press ok C:end F1 FUNCTION LIST ’installation’ set CLOCK set DATE re-configuration C-bus acknowledge all reset all EXTINGUISHING sections (details see document e1956) ok AREAS...
Overview operating menus To enter ’MAIN MENU’ press cont. F2 MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.
Overview operating menus To enter ’MAIN MENU’ press cont. F2 MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function Note F1 = press F1 ok = press ok C:end F1 FUNCTION LIST ’installation’ set CLOCK set DATE re-configuration C-bus acknowledge all reset all select GEOGRAPHICAL location ok AREAS...
Overview operating menus To enter ’MAIN MENU’ press cont. F2 MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.
Overview operating menus To enter ’MAIN MENU’ press cont. F2 MAIN MENU FIRE detection EXTINGUISHING sections CONTROL in- /outputs GEOGRAPHICAL location DEVICE level logical address (CSX no.) ok:select F1:function Note ok = press ok C:end F1 FUNCTION LIST ’installation’ set CLOCK set DATE re-configuration C-bus acknowledge all reset all logical address (CSX no.) ok area / section / zone / element 41 Siemens Building Technologies Cerberus Division e1955 11.
Siemens Building Technologies AG Cerberus Division CHĆ8708 Männedorf Alte Landstrasse 411 Tel. +ā41 1ā Ć 922 61 11 Fax +ā41 1 Ć 922 64 50 www.cerberus.ch 42 Siemens Building Technologies Cerberus Division Technologies Siemens Building Cerberus Division Cerberus Security for People and Assets Replaces PF99-041 Doc. no e1955 Back_e1955 Edition 11.1999 11.