Siemens Building Technologies 74 319 0396 0 c AST10 B5851 22.11.2011
Vmin can be adjusted in the range of –20 % ... 100 %
Siemens default setting: Vmin = 0 %
Vmax can be adjusted in the range of 20 % ... 120 %
Siemens default setting: Vmax = 100 %
The setpoint Y can be adjusted in the range of
0.00 V ... 11.00 V
The digitally adjusted setpoint has priority over the analogue
set point.
The analogue setpoint has priority again 60 seconds after
removing the connection between AST10 and
GLB/GDB/ASV181.1E/3.
The actual Air Volume Signal is displayed if U is selected. The
range is from 0.00 V ... 12.8 V and corresponds to an air
volume of 0 % (U = 0 V) to 128.0 % (U = 12.8 V).
Vn
Vmin
Vmax
TYP
DIR
Vn
Vmin
Vmax
TYP
DIR
GLB/GDB/ASV181.1E's
internal memory
Section 1
(Set Values)
Set by AST10,
ACS931 or ACS941
Section 2
(Reference Values)
Set by ACS931
The GLB/GDB/ASV181.1E/3‘s internal
memory (EEPROM) contains the parameters
set by the AST10. The memory is split in two
sections.
Section 1: contains the “Set Values”,
that are used for operation
Section 2: contains the “Reference
Values”
The AST10 allows only to change the
“Set Values”.