User Manual

11/34
Siemens Building Technologies 74 319 0396 0 c AST10 B5851 22.11.2011
The Vmin, Vmax, Y, DIR and TYP
values can be changed by using the “–”
or “+” button.The displayed value starts
blinking and can be stored during the
blink phase by pressing the “Set” button.
Confirm each input of value or read-
justment by pressing the “Set” button.
DIR can be set to either ‘L’ or ‘r’:
‘L’ means damper opens counterclockwise (rotates left)
‘r’ means damper opens clockwise (rotates right)
Siemens default setting: ‘r’
TYP can be set to either ‘con’ or ‘3P’:
‘con’ means GLB/GDB/ASV181.1E/3 is in the VAV
Controller mode.
‘3P’ means GLB/GDB/ASV181.1E/3 functions as a
separate 3 position damper actuator and differential
pressure sensor.
Siemens default setting: ‘con’
Note for VAV compact controller of series A and B:
After changing TYP from ‘3P’ to ‘con’ (or vice versa), cut
power supply to the actuator for a short period of time,
enabling the change to become active
(cut G or G0 approx. 5 s).
Vn can be adjusted in the range of 1.00 ... 2.55
Siemens default setting: Vn = 1.00
Vn changing is restricted to OEMs.
en










