User Manual

Mounting notes
When using the connecting cable with the 6-or 7-pin plug, attach the tension relief
band at the cable to the VAV compact and modular controllers as shown in the
following illustration.
1
2
3
4
5
5
6
1 AST10
2 GDB181.1E/3, GLB181.1E/3
3 GDB181.1E/KN, GLB181.1E/KN
4 ASV181.1E/3
5 Connector on AST10
6 Strain relief
Technical data
Power supply G, G0 Operating voltage AC 24 V 20 %.
Safety extra low-voltage (SELV) HD 384
(PELV) as per requirements for external
Safety isolation transformer (100 % time on)
EN 60742
Supply line fusing Max. 6 A
Frequency 50/60 Hz
Power consumption 3 VA
Signal input/output Communications signal type PPS2
Communications signal YC Protecting against incorrect connection Max. AC 24 V
Housing protection type
Protection class as per EN 60529
IP30
and -Safety class Insulation class as per EN 60730 III
Environmental conditions Operating/Transport IEC 721-3-3 / IEC 721-3-2
Climatic conditions Class 3K5 / Class 2K3
Temperature 0…50 °C / -25…70 °C
Humidity (non-condensing) <85 % r.h. / <95 % r.h.
Mechanical conditions Class 2M2
Standards and guidelines Product standards
Automatic electronic controls for EN 60730-2-14
Household and similar use (Mode of operation, type 1)
Electromagnetic compatibility
Immunity EN 61000-6-2
Emissions EN 61000-6-3
CE conformance
EMC directive 2004/108/EC
C-Tick conformity
Emissions AS/NZS 61000-6-3
Weight Without packaging 0.17 kg
Connecting cable Cable type, number of wires and diameter VDE Li-YY, 3-wire
0.34 mm
2
Cable length for cable with 6 or 7-pin plug Ca. 2.5 m
Cable length for cables with ferrules Ca. 1 m
4 / 6
Siemens Handheld tool for VAV compact controller CM1N5851en
Building Technologies 07.10.2011