User Manual
Mounting notes 
When using the connecting cable with the 6-or 7-pin plug, attach the tension relief 
band at the cable to the VAV compact and modular controllers as shown in the 
following illustration. 
1
2
3
4
5
5
6
1 AST10 
2 GDB181.1E/3, GLB181.1E/3 
3 GDB181.1E/KN, GLB181.1E/KN 
4 ASV181.1E/3 
5  Connector on AST10 
6 Strain relief 
Technical data 
Power supply G, G0  Operating voltage  AC 24 V 20 %. 
  Safety extra low-voltage (SELV)  HD 384 
  (PELV) as per requirements for external 
  Safety isolation transformer (100 % time on) 
EN 60742 
  Supply line fusing  Max. 6 A 
 Frequency  50/60 Hz 
  Power consumption  3 VA 
Signal input/output  Communications signal type  PPS2 
Communications signal YC    Protecting against incorrect connection  Max. AC 24 V 
  Housing protection type  
Protection class as per EN 60529 
IP30 
  and -Safety class  Insulation class as per EN 60730  III 
Environmental conditions  Operating/Transport  IEC 721-3-3 / IEC 721-3-2 
    Climatic conditions  Class 3K5 / Class 2K3 
      Temperature  0…50 °C / -25…70 °C 
      Humidity (non-condensing)  <85 % r.h. / <95 % r.h. 
    Mechanical conditions  Class 2M2 
Standards and guidelines  Product standards   
    Automatic electronic controls for  EN 60730-2-14 
    Household and similar use  (Mode of operation, type 1) 
 Electromagnetic compatibility  
 Immunity  EN 61000-6-2 
 Emissions  EN 61000-6-3 
 CE conformance   
 EMC directive  2004/108/EC 
 C-Tick conformity   
 Emissions  AS/NZS 61000-6-3 
Weight  Without packaging  0.17 kg 
Connecting cable  Cable type, number of wires and diameter  VDE Li-YY, 3-wire 
  0.34 mm
2
  Cable length for cable with 6 or 7-pin plug  Ca. 2.5 m 
  Cable length for cables with ferrules  Ca. 1 m 
4 / 6 
Siemens  Handheld tool for VAV compact controller  CM1N5851en 
Building Technologies    07.10.2011 