In the following, the designation VAV compact controller applies equally to the
actual VAV compact controller G..B181.1E/.. as well as the VAV modular controller
ASV181.1E/3.
Namin
g conventions
Mode of op
eration
The handheld tool is powered and the communication link between unit and VAV
compact controller is established via one of the enclosed 3-wire connecting cables.
When power is turned on, the AST10 is ready for operation after about 5 seconds,
that is, the parameters can be set and read. The LCD displays "Srch" both during
the time communication is opened – on startup – and when communication is
interrupted.
When a setting was changed, it can be saved in the VAV compact controller by
pressing the "Set" button.
When pressing the "Factory settings" button, the OEM factory settings will be
retrieved. If, in place of the factory settings, the Siemens default settings appear,
they were not overwritten by the manufacturer of the air volume controller. In the
event of communication problems with VAV compact controller, the LCD displays
"Err".
The LCD displays the available functions as follows:
Vn
V
Vmin Vmax
Y
Err
TYP U
5851Z14
%
DIR
S
Figure 1
Parameter symbols and their meaning
Sym
bol Meaning Value range
n
V
Display of key variables for nominal volumetric
airflow; set by manufacturer (OEM)
1…2,55 in increments of 0.01
Siemens factory setting: 1,00
min
V
[%]
Setting or display of minimum volumetric airflow -20…100 % in increments of
1 %
Siemens factory setting:
0 %
max
V
[%]
Setting or display of maximum volumetric airflow 20...120 % in increments of
1 %
Siemens factory setting:
100 %
Y [V]
Setting and display of setpoint of volumetric
airflow
0...11 V in increments of 0.05 V
DIR Setting or display of direction of rotation Possibilities:
r = Clockwise
L = Counterclockwise
Siemens factory setting:
r
TYP Setting or display of operating mode Possible settings: con, 3P
Siemens factory setting:
con
U [V] Display of actual value of volumetric airflow 0...12.8 V in increments of 0.05 V
S
Display of zero point calibration
(applies only to devices through series D).
Symbol blinks in display mode U and Y
2 / 6
Siemens Handheld tool for VAV compact controller CM1N5851en