Operating Instructions

Chapter 3—Applications for ATEC—VAV with Reheat
3-50 Siemens Building Technologies, Inc.
Table 3-8. Point Database for Application 2523.
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text Off Text
22 REHEAT START 0.0 PCT 0.4 0.0
23 REHEAT END 100.0 PCT 0.4 0.0
{24} DI 4 OFF ON OFF
{25} DI 3 OFF ON OFF
{29} DAY.NGT DAY NIGHT DAY
31 CLG FLOW MIN 220
(103.818)
CFM
(LPS)
4
(1.8876)
0 –
32 CLG FLOW MAX 2200
(1038.18)
CFM
(LPS)
4
(1.8876)
0 –
33 HTG FLOW MIN 220
(103.818)
CFM
(LPS)
4
(1.8876)
0 –
34 HTG FLOW MAX 2200
(1038.18)
CFM
(LPS)
4
(1.8876)
0 –
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0
36 FLOW COEFF 1.0 0.01 0.0
{40} AI 4 74.0
(23.495556)
DEG F
(DEG C)
0.5
(0.28)
37.5
(3.055556)
– –
{41} DO 1 OFF – – ON OFF
{42} DO 2 OFF – – ON OFF
{43} DO 3 OFF – – ON OFF
{44} DO 4 OFF – – ON OFF
{48} DMPR COMD 0.0 PCT 0.4 0.0
{49} DMPR POS 0.0 PCT 0.4 0.0
51 MTR1 TIMING 95 SEC 1 0
{52} VLV COMD 0.0 PCT 0.4 0.0
{53} VLV POS 0.0 PCT 0.4 0.0
55 MTR2 TIMING 130 SEC 1 0
56 DMPR ROT ANG 90 1 0
58 MTR SETUP 1 – 1 0 –
59 DO DIR. REV 0 1 0
63 CLG P GAIN 20.0 (36.0) 0.25 (0.45) 0.0
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…