Operating Instructions

Chapter 3—Applications for ATEC—VAV with Reheat
3-66 Siemens Building Technologies, Inc.
Table 3-10. Point Database for Application 2524
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
{92} CTL STPT 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{93} FLOW STPT 0.0 PCT 0.25 0.0
{94} CAL AIR NO YES NO
95 CAL SETUP 4 1 0
96 CAL TIMER 12 HRS 1 0
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0.0 –
98 LOOP TIME 5 SEC 1 0
{99} ERROR STATUS 0 1 0
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets {} may be unbundled at the field panel.