Intrinsic Alarming on ALN Panel
Intrinsic reporting allows a device to provide one or more event sources, intrinsic to the
device, which generate alarm or event notifications that may be directed to one or
more destinations.
For more information on Intrinsic Alarming, see the
APOGEE BACnet ALN Field Panel
User's Manual
(125-3020).
An Intrinsic Alarm can be created using the Point Editor application.
NOTE:
It is not recommended to add intrinsic alarms to UEC/PANEL device points.
Alarm reports can be generated using the Status Information Bar Alarm button.
1. Select the Point icon from the Create/Edit bar.
The Point Editor window opens.
2. Click Select a Panel at the top of the left pane of the Point Editor window to display
available panels.
3. Select the desired panel by clicking the panel name in the left pane of the Point
Editor window.
4. Either select an existing point or create a new point by clicking the + button at the
bottom left of the Point Editor window.
The point information window displays the point information.
5. Select the Alarmable check box to create an Intrinsic Alarm and enter related
information. See the
User Interface Description for the Point Editor Application
section for more information about related fields.
6. Click Save.
The