User Guide

Chapter 10 - Create/Edit
Point Editor Application
89
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Creating a PTEC Point
1. Select the Point icon from the Create/Edit bar.
The Point Editor window will open.
2. If available panels/devices do not display, click Select a Device at the top of the left
pane of the Point Editor window to display available panels/devices.
3. To select the desired PTEC device, click the arrows next to the supervising panel
name and next to its FLN name, and then click the PTEC device name in the left
pane of the Point Editor window. When you select a PTEC device, the object list
indicates the ability to select the Custom Point table. Select the Custom Point
Table object.
The PTEC Point Editor table displays, showing all custom points (user-defined
BACnet objects) in the PTEC device.
4. Click the + button at the bottom left of the PTEC Point Editor window.
A new row displays in the PTEC Point Editor table. The new row is configured
for an AO type point by default:
NOTE:
If the initial sort order is kept, the new row is inserted at the bottom of the table. If the
sort order has been modified, the new row is inserted at the location based on the
chosen sort order.
5. Enter the new PTEC point information.
6. Click Save.
A verification prompt displays:
7. Click Yes.
The Save button is unavailable once the modifications are complete.
NOTE:
After modifying custom points on a PTEC device, be sure to update the FLN custom
application using the Database Manager.