User Guide

Chapter 10 - Create/Edit
Point Editor Application
86
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Voltage
Current
Thermistor 10K Type 2
Thermistor 10K Type 3
Thermistor 100K
RTD 1K Platinum 375
RTD 1K Platinum 385
RTD 1K @ 32F Nickel LG-Ni
RTD 1K @ 70F Nickel JCI
RTD 1K Nickel DIN
The
Calculation Units radio buttons (LAI points only) allow you to choose from
English or S.I.
The
Slope field displays the calculated slope of the point.
The
Intercept field displays the calculated intercept of the point.
The
Calculate button uses the defined parameters to calculate the slope and
intercept of the point, and displays the results in the
Slope and Intercept fields.
The
Signal Range fields indicate the high and low value range of the signal from
the input device or to the output device. Examples: Voltage (0-10v) or current (4-20
mA).
The
Device Range fields indicate the high and low value range of units which
represent the signal range. Examples: Deg F, Deg C, PPM, %RH, and so on.
The
Wire Size field allows you to choose wire size from a selection of standard wire
sizes.
The
Wire Length field indicates the length of the wire between the sensor and the
controller in one direction.
The
Total Resistance field indicates the calculated resistance of the wire based on
the wire size and wire length or allows you to enter the total measured resistance
of the actual wire.
The OK button accepts the calculated values of slope and intercept, and populates
them in the Point Editor as defined.
The
Cancel button rejects all parameters entered in the Slope/Intercept Calculator,
and returns to the Point Editor with no changes made.
Tips for Using the Point Editor Application
During editing you cannot change the point type. For example, if you created an
LAO, it cannot be changed to an LAI.