Chapter 10 - Create/Edit
Trend Application
75
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
● The Trend Object Editor window displays on the right side of the screen.
● The
Object Name field allows you to name the Trend Object using up to 30
characters. This field is mandatory for creating a Trend Object and cannot be
edited in an existing Trend Object.
● The Object Identifier field displays the Trend Object identification information. If you
do not enter a value, the controller will automatically enter the next available Object
ID. This field cannot be edited in an existing Trend Object.
● (
Optional
) The Description field allows you to describe the point using up to 16
characters. This field can be edited.
● The
Trend Log Enabled check box allows you to enable or disable the trend log
object. This option can be edited later. This check box defaults to YES.
● The
Point to be Trended field has a drop-down menu to select the available points
in the selected panel. The
Point to be Trended field also has a question mark (?)
button that can be selected to enter a BACnet Device Object Identifier. This field
cannot be edited in existing Trend Objects.
● The Trend Type drop-down menu allows you to define the trend type (COV or
Timed). This field can be edited in existing Trend Objects.
● The
Trend Interval choices allow you to define the time interval for time-based
trends.
● The
Start Date/Time and Stop Date/Time check boxes allow you to enter a trend
start and stop Date/Time. This option can be edited in existing Trend Objects. By
default, these check boxes are not checked, so a trend start and stop Date/Time
are all wildcarded.