Chapter 5 - Point Commander Application
Point Commander Application Overview
45
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
1
Priority array for the point.
2
The Relinquish Default field displays the default value of the point. This value is
assigned to the present value when all priorities (1 through 16) are
relinquished.
3
The Present Value field shows the present value of the point at the current
highest priority, and allows you to change that value.
4
The Priority drop-down menu shows the current priority, and allows you to
change the priority. Priorities 1 through 7 are not accessible; if they are chosen,
the priority will automatically default to the highest accessible priority value.
Command Feedback
The
Feedback field at the bottom left of the window displays a message indicating the
success or failure of each action. A successful command initiates an automatic refresh
of the point values. If the command is not successful, an error message displays the
reason for the failure.
NOTICE
If the feedback status indicates a failure, an automatic refresh of the point values is
not performed.
Click the
Refresh button to manually refresh the point values before attempting a
subsequent command to the point. To troubleshoot an unsuccessful command to a
specific device, refer to the user documentation for that device.
The following figures show examples of the INVALID_DATA_TYPE and OTHER Error
Feedback messages.
Figure 2: Example of
INVALID_DATA_TYPE
Error Feedback Message.