User Guide
Chapter 5 - Point Commander Application
Point Commander Application Overview
44
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
4
Status Indicators
The following status indicators, indicate status with a check mark:
● The
In-Alarm check box indicates when the point is in an alarm status. See
the
Status Bar
section for more information.
● The
Fault check box indicates when the point is in a fault status.
● The
Overridden check box indicates when the point has been manually
overridden.
● The
Out Of Service check box indicates when the point has been disabled.
5
The Command button must be clicked to implement any changes in the
Commanding window.
6
For points with priority array, advanced command options can be accessed by
clicking the
Advanced button. The button name changes to Basic when
advanced commanding options are displayed. Click the
Basic button to toggle
back to the basic Commanding window. The left, top, and bottom sections of
the window remain the same in both views.
7
Click the Trending button to access dynamic trending for the point. For more
information, see the
Trend
[➙ 61]
section.
8
The Feedback field displays a message indicating the success or failure of
each action. A successful command initiates an automatic refresh of the point
values. If the command was not successful, an error message displays the
reason for the failure.
9
Refresh button. If the feedback status indicates a failure, click the refresh
button to manually refresh the point values. For more information, see the
Command Feedback
[➙ 45] section.
Advanced Command Options (Points with Priority Array)
If the point has priority array, the priority values can be changed through a command to
a particular priority field. The priority fields that are not applicable display as dimmed.