User Guide
Chapter 5 - Point Commander Application
Point Commander Application Overview
43
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
1
Point Name and Description
● The
Object Name field shows the point name.
● (
Optional
) The Description field displays additional point information.
● The point name, point type, data type, and instance ID displays in the
header of the Commanding window.
2
To close the Commander window, click the X in the top right corner of the
window.
3
Command Options and Status
NOTE: The information in this section is only accessible to users with
Command or higher access level to the point.
●
Present Value displays the current point value, and allows you to change
the value of commandable points.
● The
(@) field displays the current priority and allows you to change the
point priority.
NOTE: If the point does not use a priority array, the field does not display.
●
Reliability displays any faults detected. If none, then No Fault Detected
displays.
NOTE: If the point does not use the reliability property, this field does not
display.
●
Event State indicates the status of the point (Normal, Failed).
● The
Disabled check box allows you to put points in and out of service.
When a point is disabled, alarm reporting capabilities for the point are
disabled, and the
Out of Service status indicator displays a check mark.
● If totalized, the current totalized value and the last date and time the value
was reset are displayed.