User Guide

Chapter 5 - Point Commander Application
Point Commander Application Overview
43
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
1
Point Name and Description
The
Object Name field shows the point name.
(
Optional
) The Description field displays additional point information.
The point name, point type, data type, and instance ID displays in the
header of the Commanding window.
2
To close the Commander window, click the X in the top right corner of the
window.
3
Command Options and Status
NOTE: The information in this section is only accessible to users with
Command or higher access level to the point.
Present Value displays the current point value, and allows you to change
the value of commandable points.
The
(@) field displays the current priority and allows you to change the
point priority.
NOTE: If the point does not use a priority array, the field does not display.
Reliability displays any faults detected. If none, then No Fault Detected
displays.
NOTE: If the point does not use the reliability property, this field does not
display.
Event State indicates the status of the point (Normal, Failed).
The
Disabled check box allows you to put points in and out of service.
When a point is disabled, alarm reporting capabilities for the point are
disabled, and the
Out of Service status indicator displays a check mark.
If totalized, the current totalized value and the last date and time the value
was reset are displayed.