User Guide
Chapter 5 - Point Commander Application
Point Commander Application Overview
41
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Chapter 5 - Point Commander Application
Chapter 5 discusses the following topics:
● Point Commander Application Overview [➙ 41]
– User Interface Description for the Point Commander Application [➙ 42]
– Tips for Using the Point Commander Application [➙ 46]
● Using the Point Commander Application [➙ 47]
– Commanding Point Values [➙ 47]
– Disabling and Re-enabling a Point (Out of Service) [➙ 48]
– Resetting the Totalized Value [➙ 49]
– Priority Arrays [➙ 49]
Point Commander Application Overview
All points and point-like objects (AO, BO, MSO, AV, BV and MSV) with priority array
can be commanded from the BACnet Field Panel Web Server navigation tree, from a
graphic screen, and/or from a trend graph. Point value, status, and priority can be
commanded.
Point types without priority array (AI, BI, AV, BV and MSV) can be commanded from
the commander navigation tree and/or from a graphic screen. Point value and status
can be commanded.
AO
Analog Output Object
AI
Analog Input Object
BO
Binary Output Object
BI
Binary Input Object
MSO
Multi State Output Object
AV
Analog Value Object
BV
Binary Value Object
MSV
Multi State Value Object
Multi State Input Object (MSI) Points are currently not supported.
CAUTION
Command points only when you know the possible effects of making a change.
Ideally, only command points when making temporary changes, such as setpoint
changes, or when commanding modes of operation, such as DAY and NIGHT. It is
inefficient to place a point in Operator (OPER) command priority or to Disable a point
(Out of Service) for long periods of time or permanently.