User Guide
Chapter 3 - User Interface Navigation
Common Editor Fields and Buttons
35
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
For instance, if you want to create a Binary Value object with an instance of 100, you
would enter the following in the Point Editor Object Identifier:
Upon successful creation of this object, the Object Identifier field will show both
components:
The Object Identifier field cannot be modified after creation.
Object Reference
Some BACnet objects have properties that reference other BACnet objects.
For instance, an Event Enrollment object has a
Reference Point field. This field can be
filled by selecting the drop-down arrow, and selecting an object from the list, or by
selecting the
? (question mark) button and manually entering an Object Reference.
The drop-down arrow option:
The ? (question mark) button option:
Manually entering an Object Reference requires entering the instance of the Device
Object containing the desired object, and the Object Identifier of the desired object.
The above picture indicates a reference to a Binary Value object with instance 100, on
a Device with instance 1021.
Manually entering the Object Reference is required if the reference object is located in
a non-FPWeb-enabled panel or a non-FPWeb-enabled panel’s associated FLN device.