User Guide

Chapter 3 - User Interface Navigation
User Interface after Logon
31
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Clicking the green arrows to the right of the device name .
During a database discovery, status messages will display:
Static Icons
Static icons in the Device/Points bar indicate the various characteristics of the panel
node. A static icon associated with a panel node is fixed for the Web session.
Icon
Description
Indication
Red shield icon with a
horizontal white bar.
FPWeb license is not installed for the panel.
You must obtain and install an FPWeb license (LSM-
FPWEB, LSM-FPWEBPL, LSM-FPWEBPLHST) in order
to use licensed features. Moving your cursor over the
icon also indicates if the node has license restrictions: No
FPWeb license.
NOTE:
BACnet Field Panel Web Server UI requires an FPWeb
license for graphics viewing. The Device/Points
accordion Graphics folder does not expand for panels
that are not FPWeb licensed.
A purple shield icon with
a vertical white bar.
The latest firmware that the Web Server UI is aware of
has not been installed in the panel.
You must upgrade the panel to the appropriate firmware
in order to use features associated with the version of the
Web Server UI. The Panel Configuration Editor and the
ALN Node Table Editor require Firmware Revision 3.2.5
or later. The Database Manager requires Firmware
Revision 3.3 or later. Point Editing and PPCL Editing of
programmable MS/TP FLN devices require Firmware
Revision 3.3 or later.
Moving your cursor over the icon also indicates if the
node does not have the latest firmware installed: Not
latest firmware.
Both red and purple
shield icons displayed
together.
FPWeb license is not installed for the panel AND the
latest firmware has not been installed in the panel.
Moving your cursor over the icon also indicates if the
node has license restrictions and does not have the latest
firmware installed. No FPWeb license and Not
latest firmware.