User Guide
Chapter 11 - System Configuration
Panel Configuration Editor
218
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Fields that result in a coldstart when modified:
● Node Name
● ALN Name
● Device Instance Number
● BACnet IP Network Number
● UDP Port
● Changing from DHCP to Static IP
● Changing from Static IP to DHCP
● If Static IP:
– Changing the Static IP Address
– Changing the Subnet Mask
– Changing the DNS Suffix
– Changing the DNS1
– Changing the DNS2
● If configured for MS/TP (primary or secondary):
– Changing from Enable MS/TP to disabled
– Changing from disabled to Enable MS/TP
● If MS/TP is enabled:
– Changing the MS/TP FLN Network Number
– Changing the MS/TP FLN Node Address
Panels with Firmware 3.3.1 or earlier will coldstart and return to the Welcome page for
any change.