Chapter 11 - System Configuration
Panel Configuration Editor
215
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Configuring a Panel
1. Click the Panel Configuration icon from the System Configuration bar.
The Panel Configuration Editor window displays.
2. Select the desired panel by clicking the panel name in the left pane of the Panel
Configuration Editor window. Only panels that support this feature will display in
the Navigation pane.
3. Enter the panel configuration information.
If the panel has Firmware Revision 3.4 or later, and the panel is FLN
equipped and configured for P1, the
FLN Settings tab will include
configuration of each available P1 FLN port. Each port's baud rate can be
configured.
If the panel has Firmware Revision 3.3.1 or earlier, and the panel is FLN
equipped and configured for P1, the
FLN Settings tab will not include
configuration of any P1 FLN port.
If the panel has Firmware Revision 3.4 or later, and the panel is FLN
equipped and configured for MS/TP, the
FLN Settings tab will include
configuration of each available BACnet FLN port. Each port's baud rate,
network number, node address, and max master can be configured.
For more information on which physical port is primary and which is
secondary, see the
Using the Panel Configuration Editor
[➙ 214] section.
If the panel has Firmware Revision 3.3.1 or earlier, and the panel is FLN
equipped and configured for MS/TP, the
FLN Settings tab will include
configuration of only the primary BACnet FLN port. The primary port's
baud rate, network number, and node address can be configured.