User Guide

Chapter 11 - System Configuration
Panel Configuration Editor
213
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
The Baud Rate field (for MS/TP networks, active only if MS/TP FLN is enabled)
allows you to select the FLN baud rate from a drop-down menu.
MS/TP Networks Only
The
Enable MSTP FLN check box allows you to enable or disable the MS/TP FLN.
The
MSTP FLN Network Number field (active only if MS/TP FLN is enabled) allows
you to enter the network number using a number between 1 and 65534. The
BACnet IP network number and the MS/TP network numbers must not conflict with
one another. If the enabled network numbers are not unique, an error message will
display.
The
MSTP FLN Node Address field (active only if MS/TP FLN is enabled) allows
you to enter the MS/TP FLN node address (MAC address) using a number
between 0 and 127.
The
MS/TP Max Master field (active only if MS/TP FLN is enabled) specifies the
highest allowable address for master nodes. The value of Max Master must be
between 0 and 127.
FTP Server Tab (Example)
The IP Address field allows you to enter the IP address of the FTP server.
The
Username field allows you to enter a user name associated with the user
account registered with the FTP server.
The
Password field allows you to enter a password associated with the user
account registered with the FTP server.
NOTES:
- If you have no intention to use the Trend Data Upload function, there is no need to
enter information to these fields.
- If no IP Address or Username is entered, the FTP Server is considered to be
undefined. A reminder will appear in the Trend Editor if you try to enable FTP upload
for a Trend Object.
- Saving FTP Server settings will not result in a panel coldstart. The newly saved
settings will take effect upon the next FTP upload attempt.