Chapter 11 - System Configuration
Database Manager
197
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Clearing a Custom PTEC Device Application
To clear a custom PTEC device application:
1. Click the Database Manager icon in the System Configuration bar.
The Database Manager window displays. The Device radio button is selected
by default, and the
Select a device window displays under the radio buttons.
2. If desired, use the Show FLN Device Type and Show FLN Application # drop-
downs to filter the devices.
3. Select an FLN device by selecting the checkbox to the left of the FLN device name.
To the right of the device name, the application number is listed.
The Source section displays.
4. Click the Clear Custom Application button.
5. Click Yes in the Are you sure message windows to send an EMPTY database.
6. Click Yes in the Are you sure message windows to transfer files.
Message displays showing progress.