User Guide

Chapter 11 - System Configuration
Database Manager
191
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
6. Click OK.
Updating a Custom FLN Application
NOTE:
The Update feature in Database Manager will only work on UEC application
databases if all of the source and destination FLN devices have the same HIGH user
account password before attempting the Update. The HIGH user account password
must be established at the UEC device using the HMI, and the "device password" in
the supervising panel's FLN Device Reference database must be established in the
FLN editor.
Optional: Using Point Editor, modify the custom APPLICATION point list. See the
Point
Editor
section for more information.
Optional: Using PPCL Editor, modify the custom application sequence of operations.
See the
Modifying a PPCL Program
[➙ 151] section and the
APOGEE Powers
Process Control Language (PPCL) User's Manual
(125-1896) for more information.
1. To update a custom FLN application throughout the system, use Database
Manager. To update a custom FLN application from a Device source, use the
Select a Device screen and select an appropriate PTEC or UEC/PANEL device. To
update a custom FLN application from a File source, use the Select a File screen
and select appropriate files representing a PTEC or UEC/PANEL application.
An FLN Action Screen displays.
2. Click the Update button at the bottom of the Update section.
If there are devices in the device tree other than the source device, a warning
displays, indicating that these devices will receive the updated application
database.