User Guide

Chapter 11 - System Configuration
Database Manager
184
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Create/modify PTEC Custom FLN Application using Update
1. Create/modify the points of a custom PTEC FLN application using the Point Editor.
2. Create/modify the sequence of operations of a custom PTEC FLN application using
the PPCL Editor.
3. Identify the application number of the custom PTEC FLN application in the PPCL
Editor by managing a line in the PPCL.PGM.
For example, 10 APPLICATION=
XXXXX
Where
XXX
is the FLN application number in the range 12000 through 12999.
4. Use Database Manager to update the system to reflect the changes.
Create/modify UEC/PANEL Custom FLN Application using Update
1. Create/modify the points of a custom UEC/PANEL FLN application using the Point
Editor.
2. Create/modify the sequence of operations of a custom UEC/PANEL FLN
application using the PPCL Editor.
3. Identify the application number of the custom UEC/PANEL FLN application in the
Point Editor by creating/managing an Analog Value point object named
APPLICATION (all upper case) and setting the Relinquish Default value to
XXXXX
where
XXXXX
is the FLN application number in the range 10000 through11999.
4. Use Database Manager to update the system to reflect the changes.
Load
The
Load section shows all device references of the same type with an APPLICATION
number not equal to the source Custom APPLICATION number.
The Database Manager Load feature provides the ability to convert the application
running in the selected FLN device from one application to a different custom
application.
The Load feature should be used with a source that reflects an updated application:
use the
Update button before the Load button if the source is a device rather than a
file.
NOTE: Destination PTEC devices must have the same base APPLICATION number
as the source PTEC application. For example, if the source device has a base
APPLICATION 6587 and Custom APPLICATION of 12000, only destination devices
with base APPLICATION of 6587 should be selected to receive the Application 12000
database. The base APPLICATION of the destination devices is not displayed in the
Load section.