PTEC Device Source
The following example shows the user interface when a PTEC device is selected.
The source tree indicates the relationship between the source device and the system.
The Custom APPLICATION number displays the value of the APPLICATION number
managed by the PPCL.pgm program line that identifies the custom application number
in the selected PTEC.
NOTE:
If the Custom APPLICATION value displays NOT FOUND, this indicates that the
preferred workflow for PTECs to manage a line in the
PPCL.pgm was not followed for
the selected PTEC.
If the Custom APPLICATION value displays EMPTY, this indicates that there is no
custom application in the selected PTEC.
The Base APPLICATION number displays the Relinquish Default value of the
APPLICATION point, which indicates the application without customization.
The
Backup to PC button allows you to back up the PTEC application database files to
a computer.
The Clear Custom Application button allows you to send files representing an empty