Chapter 11 - System Configuration
Initial Value Editor
175
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Initializing
1. Click the Initial Value icon from the System Configuration bar.
The
Initial Value Editor window displays.
2. Select the desired panel by double-clicking the panel name or by clicking the arrow
next to the name of the desired panel in the left pane of the Initial Value Editor
window.
3. Select the desired device by clicking the arrow next to the name of the desired FLN
and then clicking the name of the desired device.
The
Points table displays.
4. Initialize the device by clicking the Initialize Device button.
The device may fail and return while it is initializing.
NOTE:
The Initial Value feature requires the correct case-sensitive password for MS/TP
device re-initialization. The password for MS/TP device re-initialization is configured
when adding/modifying an MS/TP FLN device to the field panel
Releasing Points
1. Click the Initial Value icon from the System Configuration bar.
The Initial Value Editor window displays.
2. Select the desired panel by double-clicking the panel name or by clicking the arrow
next to the name of the desired panel in the left pane of the Initial Value Editor
window.
3. Select the desired device by clicking the arrow next to the name of the desired FLN
and then clicking the name of the desired device.
The Points table displays.
4. Release points by checking the check box in the Release column of the Points
table. Multiple points can be released at the same time.
5. Click Save.
The Save button becomes grayed out once the modifications are complete.